Post Top Ad

Monday, November 13, 2023

on video 2 incoming power supply interlocking system


 A magnetic contactor is an electromechanical switch used in applications that require a circuit on and off process such as starting motors heaters and lighting applications through the switch contacts the magnetic contactor takes care of transferring energy from one place to another.

Magnetic contactor are used in the electric motors to balance the change in frequency of the motor or the state of the motor which can be termed as the switching of the motor from on and off state. Magnetic contactor act as a safeguard to protect the power supply and the motor.

why interlocking is used for the contactors?

A technique called interlocking is used to prevent the contactors from being energized simultaneously or closing together and causing a short circuit. This interlock locks out one contactor at the beginning of the stroke of either contactor to prevent short circuits and burnouts.

Substation Interlocking explained

Interlocking schemes shall cover the following conditions:-

(a) Interlocking between circuit breakers and disconnectors to ensure disconnectors do

not operate outside their rating i.e. make or break load currents.

(b) Interlocking between disconnectors and earthing switches to ensure that earthing

switches cannot be closed on to a locally energized circuit and cannot be energized,

when closed, by operation of disconnectors.

Interlocking between disconnectors and adjacent earthing switches to permit operation

of the disconnector when earthing switches are closed on both sides of the

disconnector. Such interlocking is not required for equipment rated at 145kV and

below.

(d) To ensure correct sequence of on load busbar transfer switching operations at

Multiple busbar substations.

(e) To ensure that a bus-coupler or bus-section circuit breaker is only closed with its

Associated disconnectors are both open or both closed.

(f) For equipment at sites where NGET is the Occupier, to restrict access to areas of the

substation where safety clearances may be infringed unless appropriate safety

Measures, such as isolation and earthing, have been taken

1.1.4 The interlocking of switching sequences involving only power operated switchgear shall be

by electrical means. The correct interlocking status shall be confirmed automatically oninitiation of an operation from any control position or from auto-switching or sequential isolation equipment.

1.1.5 The interlocking of switching sequences involving manually operated switchgear may be by

electrical or mechanical means. The interlocking shall be designed such that the correct

Interlocking status must be confirmed immediately before an operation.

1.1.6 Interlocking systems shall, where reasonably practicable, be fail-safe. They shall not be

defeated without the use of tools, clip leads etc. or a purpose designed override facility.

1.1.7 Interlock override facilities shall be lockable with a unique lock or shall be lockable by means

of a safety padlock.

1.1.8 Partial interlocking of earthing switches at circuit-entries to the substation is acceptable

where it is not reasonably practicable to extend the interlocking to the remote end

disconnectors. Any partially interlocked earthing switch shall be provided with a warning

label stating 'WARNING, THIS EARTHING SWITCH IS NOT FULLY INTERLOCKED'.

1.1.9 Interlocking shall be effective for switching and operating sequences when they are being

followed in either direction (for example; if an earthing switch must be closed before an

access gate can be opened then the gate must be secured closed before the earthing switch

can be opened).

1.1.10 Interlocking schemes shall, where reasonably practicable, provide the maximum operational

Flexibility and shall not unnecessarily impose fixed operating sequences.

1.1.11 Where an interlocking scheme is being supplied for an extension to an existing substation

  at the same operating voltage then, unless otherwise agreed by NGET, the interlocking

philosophy shall match that existing.

1.1.12 Interlocking for a substation extension shall be fully interfaced with the existing interlocking

scheme to achieve the functional requirements specified in this document.

1.1.13 Interlocking may, in certain circumstances, have to be by-passed by auto-reclose schemes.

The requirements for these are specified in TS 3.24.16. (RES).

1.2 Mechanical Interlocking

1.2.1 Mechanical interlocking systems shall be designed to provide a level of security and

Reliability comparable with equipment specified in Clauses 1.2.2 to 1.2.6 below.

1.2.2 Mechanical interlocking shall be by key operated systems

1.2.3 Interlock keys shall be of a non-masterable design (i.e. no master key can be supplied or

manufactured). Differs shall not be repeated on the same substation site.

Note: Differ is the term for the difference in a key which prevents it being

interchangeable with another.

1.2.4 Interlock keys shall be engraved with an identifying reference which shall be unique to that

substation site. The identifier shall, where appropriate, include the system number of the

switching device where the key is located during normal operation. Key locations shall be

Marked with the identifier of the required key.

1.2.5 Where key exchange boxes are provided they shall be located in convenient positions with

Regarding normal substation operating sequences.

1.2.6 Where mechanical key interlocking is fitted to disconnector and earthing switch mechanisms

The requirements specified in TS 3.2.2 (RES) shall apply.

1.3 Electrical Interlocking

1.3.1 Electrical interlocking systems shall be designed to provide a level of security and reliability

Comparable with equipment specified in Clauses 1.3.2 and 1.3.3 below.

1.3.2 A facility shall be provided to allow the interlock system of each disconnector or earthing

switch to be defeated without disturbing wiring. The facility shall meet the requirements of

Clause 1.1.7


 A magnetic contactor is an electromechanical switch used in applications that require a circuit on and off process such as starting motors heaters and lighting applications through the switch contacts the magnetic contactor takes care of transferring energy from one place to another.

Magnetic contactor are used in the electric motors to balance the change in frequency of the motor or the state of the motor which can be termed as the switching of the motor from on and off state. Magnetic contactor act as a safeguard to protect the power supply and the motor.

why interlocking is used for the contactors?

A technique called interlocking is used to prevent the contactors from being energized simultaneously or closing together and causing a short circuit. This interlock locks out one contactor at the beginning of the stroke of either contactor to prevent short circuits and burnouts.

Substation Interlocking explained

Interlocking schemes shall cover the following conditions:-

(a) Interlocking between circuit breakers and disconnectors to ensure disconnectors do

not operate outside their rating i.e. make or break load currents.

(b) Interlocking between disconnectors and earthing switches to ensure that earthing

switches cannot be closed on to a locally energized circuit and cannot be energized,

when closed, by operation of disconnectors.

Interlocking between disconnectors and adjacent earthing switches to permit operation

of the disconnector when earthing switches are closed on both sides of the

disconnector. Such interlocking is not required for equipment rated at 145kV and

below.

(d) To ensure correct sequence of on load busbar transfer switching operations at

Multiple busbar substations.

(e) To ensure that a bus-coupler or bus-section circuit breaker is only closed with its

Associated disconnectors are both open or both closed.

(f) For equipment at sites where NGET is the Occupier, to restrict access to areas of the

substation where safety clearances may be infringed unless appropriate safety

Measures, such as isolation and earthing, have been taken

1.1.4 The interlocking of switching sequences involving only power operated switchgear shall be

by electrical means. The correct interlocking status shall be confirmed automatically oninitiation of an operation from any control position or from auto-switching or sequential isolation equipment.

1.1.5 The interlocking of switching sequences involving manually operated switchgear may be by

electrical or mechanical means. The interlocking shall be designed such that the correct

Interlocking status must be confirmed immediately before an operation.

1.1.6 Interlocking systems shall, where reasonably practicable, be fail-safe. They shall not be

defeated without the use of tools, clip leads etc. or a purpose designed override facility.

1.1.7 Interlock override facilities shall be lockable with a unique lock or shall be lockable by means

of a safety padlock.

1.1.8 Partial interlocking of earthing switches at circuit-entries to the substation is acceptable

where it is not reasonably practicable to extend the interlocking to the remote end

disconnectors. Any partially interlocked earthing switch shall be provided with a warning

label stating 'WARNING, THIS EARTHING SWITCH IS NOT FULLY INTERLOCKED'.

1.1.9 Interlocking shall be effective for switching and operating sequences when they are being

followed in either direction (for example; if an earthing switch must be closed before an

access gate can be opened then the gate must be secured closed before the earthing switch

can be opened).

1.1.10 Interlocking schemes shall, where reasonably practicable, provide the maximum operational

Flexibility and shall not unnecessarily impose fixed operating sequences.

1.1.11 Where an interlocking scheme is being supplied for an extension to an existing substation

  at the same operating voltage then, unless otherwise agreed by NGET, the interlocking

philosophy shall match that existing.

1.1.12 Interlocking for a substation extension shall be fully interfaced with the existing interlocking

scheme to achieve the functional requirements specified in this document.

1.1.13 Interlocking may, in certain circumstances, have to be by-passed by auto-reclose schemes.

The requirements for these are specified in TS 3.24.16. (RES).

1.2 Mechanical Interlocking

1.2.1 Mechanical interlocking systems shall be designed to provide a level of security and

Reliability comparable with equipment specified in Clauses 1.2.2 to 1.2.6 below.

1.2.2 Mechanical interlocking shall be by key operated systems

1.2.3 Interlock keys shall be of a non-masterable design (i.e. no master key can be supplied or

manufactured). Differs shall not be repeated on the same substation site.

Note: Differ is the term for the difference in a key which prevents it being

interchangeable with another.

1.2.4 Interlock keys shall be engraved with an identifying reference which shall be unique to that

substation site. The identifier shall, where appropriate, include the system number of the

switching device where the key is located during normal operation. Key locations shall be

Marked with the identifier of the required key.

1.2.5 Where key exchange boxes are provided they shall be located in convenient positions with

Regarding normal substation operating sequences.

1.2.6 Where mechanical key interlocking is fitted to disconnector and earthing switch mechanisms

The requirements specified in TS 3.2.2 (RES) shall apply.

1.3 Electrical Interlocking

1.3.1 Electrical interlocking systems shall be designed to provide a level of security and reliability

Comparable with equipment specified in Clauses 1.3.2 and 1.3.3 below.

1.3.2 A facility shall be provided to allow the interlock system of each disconnector or earthing

switch to be defeated without disturbing wiring. The facility shall meet the requirements of

Clause 1.1.7

No comments:

Post a Comment

Post Top Ad

Pages